Related Permit Details
Application/Permit Information
Application/Permit Number:
Application Type:
Application Date:
Status:
Project Name:
Project Description:
Type | Status | Outcome | Cost | Date | Inspector | Checklist | Inspector Notes | General Notes |
---|---|---|---|---|---|---|---|---|
Electrical - Rough In | Available | |||||||
Electrical - Final | Available | |||||||
Electrical - Spot Check | Available | |||||||
Electrical - Service Pole | Available | |||||||
Electrical - Temporary Service | Failed | Disapproved | July 23, 2021 9:22 AM | Richard Windon | 4th fl units only...all sheetrock will need to be 100% completed ..panel more than 1/4'' in wall will need to be corrected...seal around panels....if all breakers are terminated than devices and plates will need top b 100% completed or take cir off breaker and cap in panel...this inspection is for units only, EC will call for meter inspection after all units are completed | |||
Electrical - Above Ceiling | Available | |||||||
Electrical - Stocking | Available | |||||||
Electrical - Underground | Available | |||||||
Electrical - Panels/Service | Available | |||||||
Electrical - Roof Top | Available | |||||||
Electrical - Floor Heat | Available | |||||||
Electrical - Temporary Service | Passed | Approved | July 26, 2021 8:28 AM | Richard Windon | 4th fl units only | |||
Electrical - Temporary Service | Passed | Approved | July 29, 2021 1:50 PM | Richard Windon | 3rd fl units only not meters | |||
Electrical - Temporary Service | Passed | Approved | August 5, 2021 11:40 AM | Richard Windon | 2nd fl units only not meters | |||
Electrical - Temporary Service | Passed | Approved | August 6, 2021 9:16 AM | Richard Windon | 1st fl units only not meters | |||
Electrical - Temporary Service | Failed | Disapproved | August 10, 2021 10:01 AM | Richard Windon | 1. bond neutral and grounds and GEC together in all service disconnects...2.separate neutrals and grounds in all panels and meters on load side of service disconnects...3.need cold water bond to go to service disconnects...4.bond ct cabinet.... will need full inspection once this is completed | |||
Electrical - Temporary Service | Passed | Approved for Occupancy | August 12, 2021 1:48 PM | Richard Windon |