Type | Status | Outcome | Cost | Date | Inspector | Checklist | Inspector Notes | General Notes |
---|---|---|---|---|---|---|---|---|
Mechanical - Gas Piping | Available | |||||||
Mechanical - Hood | Available | |||||||
Mechanical - Replacement | Available | |||||||
Mechanical - Above Ceiling | Available | |||||||
Mechanical - Rough In | Failed | Disapproved | June 13, 2023 11:14 AM | David Tapp | 1--fire dampers must be framed and installed per manuf installation instructions----provide instructions---2--check requirements for break away connections-3---provide contact name and number when scheduling inspection | |||
Mechanical - Spot Check | Available | |||||||
Mechanical - Final | Canceled | Not Applicable | June 13, 2023 11:14 AM | David Tapp | ||||
Mechanical - Other | Available | |||||||
Mechanical - Stocking | Available | |||||||
Mechanical - Duct Seal | Available | |||||||
Mechanical - Final | Failed | Disapproved | July 18, 2023 10:04 AM | David Tapp | screws in fire damper flashing needs to be spaced per manuf installation instructions | |||
Mechanical - Rough In | Canceled | Not Applicable | June 20, 2023 2:56 PM | David Tapp | leave fire damper installation instructions on site with the builder | |||
Mechanical - Rough In | Failed | Disapproved | June 21, 2023 1:58 PM | David Tapp | fire dampers not installed per manuf installation instructions--Vertical fire damper installations require the dampers are installed with the blades at the top not the side --wall installations are not horizontal | |||
Mechanical - Rough In | Passed | Approved | June 23, 2023 1:18 PM | David Tapp | ||||
Mechanical - Final | Passed | Approved for Occupancy | July 19, 2023 11:24 AM | David Tapp | Nine fire dampers |