Related Permit Details
Application/Permit Information
Application/Permit Number:
Application Type:
Application Date:
Status:
Project Name:
Project Description:
Type | Status | Outcome | Cost | Date | Inspector | Checklist | Inspector Notes | General Notes |
---|---|---|---|---|---|---|---|---|
Plumbing - Water Heater | Available | |||||||
Plumbing - Water Service | Available | |||||||
Plumbing - Below Slab | Failed | Disapproved | October 20, 2022 8:38 AM | Michael Jar | Need stamp drawing on site and then we can do inspection. | |||
Plumbing - Rough In | Failed | Disapproved | September 6, 2023 11:21 AM | Chris Clark | Several fiberglass tubs need to be secured though out the entire building, No test on DWV, Missing mid strap on vent pipe on the third floor ( Units are not marked ) ****Note: Building one is still missing a plumbing permit. See inspection notes, listed on this same permit, from 5/5/23 inspection.***** SB | |||
Plumbing - Spot Check | Available | |||||||
Plumbing - Final | Available | |||||||
Plumbing - Irrigation | Available | |||||||
Plumbing - Above Ceiling | Available | |||||||
Plumbing - Sewer | Available | |||||||
Plumbing - Storm Drainage | Available | |||||||
Plumbing - Stocking | Available | |||||||
Plumbing - Below Slab | Passed | Approved | October 21, 2022 12:21 PM | Michael Jar | ||||
Plumbing - Below Slab | Failed | Disapproved | October 27, 2022 10:50 AM | Chris Clark | Hot and cold water lines can not be bundled together, stand pipe for 2 inch p traps can not be over 24 inchs to the fixture outlet | |||
Plumbing - Below Slab | Passed | Approved | October 31, 2022 11:02 AM | Chris Clark | ||||
Plumbing - Below Slab | Failed | Disapproved | May 5, 2023 1:45 PM | Shane Broadhurst | Need a permit for building 1, as this permit is for building 3. Today's inspection was scheduled for bldg 1, which has no permit (work begun without permit). Note: Told plumbing contractor onsite it was ok to cover plumbing below slab on bldg 1 - plumbing is good. | |||
Plumbing - Rough In | Canceled | Not Applicable | September 8, 2023 12:00 AM | Chris Clark | ||||
Plumbing - Rough In | Failed | Disapproved | September 12, 2023 9:31 AM | Chris Clark | No test on DWV, ( Water is tested though the roof, no access to roof, un safe, could not verify test, Please put test 3 foot above the highest fixture on the third floor ) Side note: See previous inspection notes, plumbing permit for building 1 is required. | |||
Plumbing - Rough In | Passed | Approved | September 15, 2023 10:38 AM | Chris Clark | Building 3 complete ///Side Note: I was advised that the plumbing contractor is not installing the water and sewer service to the buildng. I advised him that there has not been a plumbing permit pulled for the outside water and sewer service. We will need this permitted and inpected.///On hold until water and sewer lines are permitted by utility contractor. CB/// |