Type | Status | Outcome | Cost | Date | Inspector | Checklist | Inspector Notes | General Notes |
---|---|---|---|---|---|---|---|---|
Electrical - Rough In | Failed | Disapproved | 100 | November 3, 2022 8:55 AM | Preston Byrd | Not ready. Wall spacing, NM cable hanging, Strapping of NM cable. | ||
Electrical - Rough In | Failed | Disapproved | November 7, 2022 9:43 AM | Preston Byrd | No access, doors are screwed closed. | |||
Electrical - Spot Check | Available | |||||||
Electrical - Service Pole | Available | |||||||
Electrical - Temporary Service | Available | |||||||
Electrical - Above Ceiling | Available | |||||||
Electrical - Stocking | Available | |||||||
Electrical - Underground | Available | |||||||
Electrical - Panels/Service | Available | |||||||
Electrical - Roof Top | Available | |||||||
Electrical - Floor Heat | Available | |||||||
Electrical - Final | Failed | Disapproved | 100 | May 24, 2023 12:04 PM | Preston Byrd | 1. Recept plate missing in living room to left of water heater. 2. Need fire ring of boxes not within 1/4" of finished surfaces in living room and disposal recept. 3. Reidentify white wire in water heater. 4. Need recept within 24" of end of countertop for wall spacing at penisular. 5. Label dishwasher disconnect. 6. Recept within 6 feet of kitchen sink in dining room needs GFI protection. 7. 2nd ground rod needs to be below grade. 8. Hood fan needs 15 amp MOCP. 9. A/C disconnect needs to be within sight of A/C or lockable. 10. Exterior recept not label in panel or GFI protected. | ||
Electrical - Rough In | Failed | Disapproved | November 14, 2022 3:24 PM | Preston Byrd | 1. Nail plate gaps and holes not covering NM cable, 1 st floor bathroom top plate, At service panel behind range, at top plate above panel on 2nd floor. 2. Strap NM cable within 8" of recept on 2nd floor bedroom at top of stairs. | |||
Electrical - Rough In | Failed | Disapproved | 100 | November 18, 2022 9:20 AM | Preston Byrd | Not all corrections made. 1. Nail plate gaps and holes not covering NM cable, 1 st floor bathroom top plate, at top plate above panel on 2nd floor. 2. Strap NM cable within 8" of recept on 2nd floor bedroom at top of stairs. | ||
Electrical - Rough In | Failed | Disapproved | 200 | November 23, 2022 1:56 PM | Preston Byrd | Not all corrections made from previous inspection. 1. Nail plate gaps and holes not covering NM cable, at top plate above panel on 2nd floor. Where home runs are. Wall is marked. 2. Strap NM cable within 8" of all recept in 2nd floor bedroom at top of stairs. | ||
Electrical - Rough In | Canceled | Not Applicable | November 29, 2022 12:00 AM | Preston Byrd | ||||
Electrical - Rough In | Passed | Approved | November 29, 2022 8:19 AM | Preston Byrd | corrections | |||
Electrical - Final | Passed | Approved for Occupancy | June 1, 2023 8:46 AM | Preston Byrd |