Application/Permit Details

Application/Permit Information
Application/Permit Number:
Application Type:
Application Date:
Status:
Project Name:
Status Date:
Project Description:
Fee:
Permit Available Digitally
6910 Fayetteville Road, #400
Name Role
Southpoint Mall Llc Registered Owner
Permitflow Applicant
Fulcrum Construction, Llc Contractor
PID PIN
244638 0718648392
Approved Department Status Status Date Comments
Building Inspections Disapproved August 22, 2024 3:46 PM Permit # 24103473 reviewed by Doug Wegner on August 22 is Disapproved. Note the following concerns. 1. Life Safety plan sheet L.S.1.0 defines an exit path going through stock room 133. Review this condition with the NCBC section 1016 item 5. 2. Similar to item # 1 above , re-evaluate exit path at stock room 117. 3. Provide contractor with design details for guards , shown on page A9.11. 4. Evaluate the need for cane rail in at the stair area shown on sheet A7.8 C 5. Re-evaluate keyed locking mechanism on coil door showm at mall entrance on sheet A13.0b. See NCBC section 402.8.8 Send all communication/revisons to Plansreview@DurhamNC.gov . In the e-mail subject line provide the permit number.Do not send through D plans portal.
Building Inspections - Electrical Disapproved August 15, 2024 8:18 AM electrical room 131 door needs to open out and be provided with panic hardware----will need gfi in room 131----larry.vaughan@durhamnc.gov
Building Inspections - Plumbing Disapproved August 20, 2024 9:26 AM Remove all gas plans as from plumbing plans as stated in the check list. Send corrected plumbing only plans to plumbingplanreview@durhamnc.gov. CB
Building Inspections - Mechanical Disapproved August 16, 2024 8:08 AM All gas plans are to be reviewed by the mechanical department- removed gas from plumbing drawings and resubmit in the portal and copy directly to me at Willie.hunter@durhamnc.gov- wjh
Building Inspections - City Fire Approved August 15, 2024 4:36 PM Sprinkler and fire alarm permit required. MBM 8/15/24
Department Of Water Management - Cross Connection Control Approved August 20, 2024 11:08 AM 8/29/24: If domestic shut off valve is not holding, Dick's/Transform is responsible for replacement prior to CO. MNH Existing domestic to remain. New fire backflow being designed and permitted currently. CO contingent upon passing Fire backflow inspection by CCC. CCN: 4N24-W2NX (C) MNH
Final Approved October 7, 2024 5:15 PM
Building Inspections - Electrical Approved September 27, 2024 3:06 PM LV
Building Inspections - Mechanical Approved August 19, 2024 7:20 AM wjh
Building Inspections - Plumbing Disapproved August 21, 2024 1:18 PM Remove all gas plans as from plumbing plans as stated in the check list. Send corrected plumbing only plans to plumbingplanreview@durhamnc.gov. CB
Building Inspections - Plumbing Approved September 4, 2024 6:43 AM CB
Building Inspections Comments September 16, 2024 9:13 AM Permit # 24103473 reviewed by Doug Wegner on September 16th is Disapproved. Note the following Provide further clarification on the egress dynamics at the mall entrance. Upon closer review it appears that the placement of the egress signs at the storage room doors are actually in the storage room and the egress door swings into the storage rooms which have less than 50 occupants ( 117, 114 ) . Less than 50 occupants door swing is acceptable. Clarify exit distance ,and exit discharge for occupants in storage room 114. Send all communication to Plansreview@DurhamNC.gov In the e-mail subject line provide the permit number.
Building Inspections Approved October 7, 2024 3:40 PM Permit # 24103473 reviewes by Doug Wegner on October 7 is Approved.
Type Required Status Received Received Date
3 Drawings (Copies) Yes Complete Yes August 20, 2024 11:00 AM
Department Status Required Inspection Date Inspector Comments Sign Off Date
Building Approved for Occupancy Yes August 27, 2025 Karey McConnell August 27, 2025
Electrical Approved for Occupancy Yes August 27, 2025 Chris Januzys See Electrical permit for Comments on Food Truck Outlets August 27, 2025
Plumbing Approved for Occupancy Yes July 17, 2025 Michael Jar July 17, 2025
Mechanical Approved for Occupancy Yes August 14, 2025 Mike Newport August 14, 2025
City Fire Prevention Approved for Occupancy Yes August 25, 2025 Michael Kromer August 26, 2025
Cross Connection Approved for Occupancy Yes August 27, 2025 Terry Sparrow 7/21/25 Domestic dripping, it is failing and needs repaired and re-tested. 8/29/24: If domestic shut off valve is not holding, Dick's/Transform is responsible for replacement prior to CO August 27, 2025