Building Inspections |
Disapproved |
September 24, 2021 2:31 PM |
Permit # 21104742 reviewed by Doug Wegner on September 24 2021 is Disapproved. Note this review was completed remotely and the reviewer maybe reached at 919-323-6658 .
Note the following :
Provide additional information to address /clarify the grade level of the exit discharge at both exits. Attempts to view the property VIA Durham County GIS were not successful . Pictures/ relative grade elevations should clarify the concern.
Send all communication to Doug.Wegner@DurhamNC.gov ; In the e-mail subject line provide the permit number. |
|
Final |
Approved |
October 14, 2021 12:00 AM |
MPC |
|
Building Inspections - Electrical |
Approved |
September 22, 2021 10:50 AM |
LV |
|
Building Inspections - Plumbing |
Disapproved |
September 22, 2021 10:57 AM |
Many fixtures are not vented per 2018 NC Plumbing code. Cannot have horizontal dry vents as well. Please show 60 inch clear floor space for each ADA toilet. Need to show transfer shower elevation and dimensions. Send corrections to plumbingplanreview@durhamnc.gov. cb |
|
Building Inspections - Mechanical |
Approved |
September 22, 2021 1:22 PM |
Review NC mechanical code 307.2.5 for Drain Line maintenance / wjh |
|
Building Inspections - City Fire |
Approved |
September 22, 2021 10:36 AM |
MPC |
|
Department Of Water Management - Cross Connection Control |
Disapproved |
September 22, 2021 12:49 PM |
Effective 11/1/2017, CCC will implement a $150.00 fee to perform plan review and re-review(s) associated with received building permit applications to the City/County Inspections Department. Use this link to receive details on how to apply for a CCC plan review application. <https://durhamnc.gov/DocumentCenter/View/31096/LDO-Instructions---Plan-Review?bidId>=
|
|
Planning Department |
Approved |
September 30, 2021 12:00 AM |
RWG 9/30/2021 |
|
Building Inspections - Plumbing |
Disapproved |
October 4, 2021 12:52 PM |
Fixtures are still not vented correctly. Cannot have horizontal dry vents in NC plumbing code. Washer must be a 3 inch drain per NC plumbing code. Send corrections to plumbingplanreview@durhamnc.gov. cb |
|
Department Of Water Management - Cross Connection Control |
Approved |
September 24, 2021 2:31 PM |
New RPZ for suite isolation in Coach's Lounge 107 with drain to floor drain. MNH
|
|
Building Inspections |
Disapproved |
September 29, 2021 1:45 PM |
Permit # 21104742 reviewed by Doug Wegner on September 29th is Disapproved. Note this review was completed remotely and the reviewer maybe reached at 919-323-6658.
Note the following :
Clarify the design intent in terms of sprinkler system. It appears that this is project is a change of use from an S-2 to A-3 . Per table 1012.2.1 and paragraph 1012.2.1.1 of the 2018 NCEBC the proposed area would have to be sprinklered.
Send all communication /revisions to Doug.Wegner@DurhamNC.gov |
|
Building Inspections |
Approved |
September 30, 2021 11:26 AM |
Permit # 21104742 reviewed by Doug Wegner on September 30th 2021 is Approved. Note this review was completed remotely and the reviewer maybe reached at 919-323-6658. |
|
Building Inspections - Plumbing |
Approved |
October 14, 2021 10:34 AM |
cb |